Historical Standard: Standard Test Method for Flash and Fire Points by Cleveland Open Cup Tester

ASTM D92

Scope

1.1 This test method describes the determination of the flash and fire point of petroleum products by a manual Cleveland open cup apparatus or an automated Cleveland open cup apparatus.

Note 1—The precisions for fire point were not determined in the current interlaboratory program. Fire point is a parameter which is not commonly specified, although in some cases, knowledge of this flammability temperature may be desired.

1.2 This test method is applicable to all petroleum products with flash points above 79° C (175° F) and below 400° C (752° F) except fuel oils.

Note 2—This test method may occasionally be specified for the determination of the fire point of a fuel oil. For the determination of the flash points of fuel oils, use Test Method D 93. Test Method D 93 should also be used when it is desired to determine the possible presence of small, but significant concentrations of lower flash point substances which may escape detection by Test Method D 92. Test Method D 1310 can be employed if the flash point is known to be below 79° C (175° F).

1.3 The values stated in SI units are to be regarded as the standard. The values given in parentheses are for information only.

1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific hazard statements, see 6.4, 7.1, 11.1.3, and 11.2.4.