Shopping Cart

No products in the cart.

BS EN 61378-1:2011:2012 Edition

$215.11

Convertor transformers – Transformers for industrial applications

Published By Publication Date Number of Pages
BSI 2012 96
Guaranteed Safe Checkout
Category:

If you have any questions, feel free to reach out to our online customer service team by clicking on the bottom right corner. We’re here to assist you 24/7.
Email:[email protected]

This Part of IEC 61378 deals with the specification, design and testing of power transformers and reactors which are intended for integration within semiconductor converter plants; it is not applicable to transformers designed for industrial or public distribution of a.c. power in general.

The scope of this International Standard is limited to application of power converters of any power rating. Typical applications are: thyristor rectifiers for electrolysis; diode rectifiers for electrolysis; thyristor rectifiers for large drives; thyristor rectifiers for scrap melting furnaces, and diode rectifiers feeding inverters for variable speed drives. The standard also covers the regulating unit utilized in such application as step down regulating transformers or autotransformers. The valve winding highest voltage for equipment is limited to 36 kV.

This standard is not applicable to transformers for HVDC power transmission. These are highvoltage transformers, and they are subjected to d.c. voltage tests.

The standards for the complete converter plant (IEC 60146 series, or other publications dedicated to particular fields of application) may contain requirements of guarantees and tests (such as insulation and power loss) for the whole plant, including the converter transformer and possibly auxiliary transformers and reactor equipment. This does not relieve the application of the requirements of this standard concerning the guarantees and tests applicable to the converter transformer itself as a separate component before being assembled with the remainder of the converter plant.

The guarantees, service and type tests defined in this standard apply equally to transformers supplied as part of an overall converter package, or to those transformers ordered separately but for use with converter equipment. Any supplementary guarantee or special verification has to be specifically agreed in the transformer contract.

The converter transformers covered by this standard may be of the oil-immersed or dry-type design. Unless specific exceptions are stated in this standard, the transformers comply with IEC 60076 series for oil-immersed transformers, and with IEC 60076-11 for dry-type transformers.

NOTE For some converter applications, it is possible to use common distribution transformers of standard design. The use of such standard transformers in the special converter applications may require a certain derating. This matter is not specifically covered in this standard, which deals with the requirements to be placed on specially designed units. It is possible to estimate this derating from the formulae given in 5.1, and also from Clause 9 of IEC 60076-8:1997.

This standard deals with transformers with one or more active parts installed in the same tank like regulating (auto)transformer and one or two rectifier transformers. It also covers transformers with transductors and/or one or more interphase transformers.

For any combination not listed above an agreement between the purchaser and manufacturer is necessary regarding the determination and the measurement of the total losses.

This standard deals with transformers star Y and delta D and any other phase shifting connections (like zig-zag, extended delta, polygon etc.). Phase shifting windings can be placed on either the regulating or rectifier transformer.

PDF Catalog

PDF Pages PDF Title
6 CONTENTS
10 FOREWORD
12 1 Scope
13 2 Normative references
3 Terms, definitions and acronyms
3.1 Terms and definitions
14 3.2 Acronyms
Figures
Figure 1 – B6U or DB 6 pulse double bridge connection
15 4 Classification
4.1 General
4.2 Normal service conditions
Figure 2 – DSS 6 pulse connection
16 4.3 Provision for unusual service conditions
5 Ratings
5.1 General
5.2 Rated power at rated frequency and load capability
17 5.3 Rated and service voltages
5.4 Rated current
5.5 Phase displacement and terminal identification for three-phase transformer
18 5.6 Rating plate
5.7 Units with tertiary windings loaded with filter and compensation
19 5.8 On load tap-changers
6 Load loss and voltage drop in transformers and reactors
6.1 General
6.2 Determination of transformer load loss under distorted current loading
23 6.3 Current sharing, losses and hot spot in high current windings
24 6.4 Effect of geometrical winding arrangement and magnetic coupling between windings on their eddy current losses due to harmonics in transformers with three or more windings wound on the same core limb
26 Figure 3 – Leakage fields for a three-winding transformerwith closely coupled valve windings
27 Figure 4 – Leakage fields for a three-winding transformer with decoupled valve windings
28 Figure 5 – Leakage fields for a three winding transformer with loosely coupled double concentric valve windings
29 Figure 6 – Leakage fields for a three winding transformer with loosely coupled double-tier valve windings
30 6.5 Losses in interphase transformers, current-balancing reactors, series-smoothing reactors and transductors
31 6.6 Voltage drops in transformers and reactors
32 Figure 7 – Typical transductor regulating curve (with max voltage drop at zero control current) and tolerance band
33 7 Tests for converter transformers
7.1 General
34 7.2 Measurement of commutating reactance and determination of the inductive voltage drop
35 7.3 Measurement of voltage ratio and phase displacement
7.4 Dielectric tests
36 7.5 Load loss test
7.6 Temperature rise tests
39 8 On load noise level with transductors and/or IPT
40 Tables
Table 1 – Connections and calculation factors
42 Annex A (informative) Determination of transformer service load loss at rated non-sinusoidal converter current from measurements with rated transformer current of fundamental frequency
44 Figure A.1 – Cross-section of a winding strand
45 Table A.1 – Specified harmonic currents and phase displacement in the valve windings
46 Table A.2 – Resistance measurements at 20 °C winding temperature
47 Figure A.2 – Terminal identification for winding connection Y y0y6
49 Table A.3 – Specified harmonic currents and phase displacementin the line and valve windings
50 Figure A.3 – Terminal identification for winding connection D d0y1
Table A.4 – Measurements from test report
51 Figure A.4 – Valve current DB connection rectangular shape positive shape
52 Figure A.5 – Valve current DB connection rectangular shape positive and negative shape
Table A.5 – Resulting current harmonics
53 Table A.6 – Resulting current harmonics
54 Table A.7 – Resulting current harmonics
55 Table A.8 – Detailed transformer load losses at rated tap position, with tertiary unloaded
56 Figure A.6 – Valve current DSS connection rectangular shape
Table A.9 – Resulting current harmonics
57 Table A.10 – Specified harmonic currents and phase displacementin the line and valve windings
58 Table A.11 – Resulting current harmonics
59 Table A.12 – Detailed transformer load lossesat rated tap position, with tertiary unloaded
60 Annex B (informative) Short-circuit test currents and load losses in transformersfor single-way converters (total loss injection)
61 Annex C (informative) Current sharing measurement in high current valve windings
62 Figure C.1 – Example of valve high current windingand measurement equipment disposition
63 Figure C.2 – Transformer windings arrangement
64 Figure C.3 – Measurement circuit for the in-phase measurement
65 Figure C.4 – Measurement circuit for the in-opposition measurement
66 Table C.1 – Measurements and comparison with the simulations madeby finite element method software for the in-phase current distribution
67 Figure C.5 – Measurements and comparison with the simulations madeby finite element method software for the in-phase current distribution
68 Table C.2 – Measurements and comparison with the simulations made by finite element method software for the in-opposition current distribution
69 Figure C.6 – Measurements and comparison with the simulations madeby finite element method software for the in-opposition current distribution
70 Annex D (informative) Examples of duty cycles
Table D.1 – Examples of duty cycles for different applications
71 Annex E (informative) Guidelines for design review
74 Annex F (informative) Determination of loss in transformer tank due to magnetic field. 3D simulation and guidelines for tank losses evaluation and tank hotspot calculation
75 Annex G (informative) Short-circuit measurements of rectifier transformers equippedwith built in transductors
77 Annex H (informative) Determination of the transformer voltage ratio and phase displacementby the turn ratio measurements
Table H.1 – Single phase ratio measurements
78 Figure H.1 – Yd1 connection
Figure H.2 – Yd11 connection
79 Figure H.3 – Pd0+7,5 connection
80 Figure H.4 – Oscilloscope connection
Figure H.5 – Oscilloscope with phase B + 7,5° lag referring to phase A
81 Figure H.6 – Oscilloscope with phase B – 7,5° lead referring to phase A
82 Annex I (informative) Phase displacement connections and terminal indicationsof converter transformers
Figure I.1 – Counterclockwise phase displacement
Figure I.2 – Yd11 connection
Figure I.3 – Yd1 connection
83 Figure I.4 – Example I.1 phase displacement
Figure I.5 – Example I.2 phase displacement
87 Annex J (normative) Correlation between IEC 61378-1 and IEC 60146-1-1 ratings
Figure J.1 – DB connection ideal rectangular current blocks
88 Figure J.2 – DSS Connection rectangular current blocks
Table J.1 – Harmonics content up to 25th in DB 6 pulse connection(ideal rectangular current waveshape)
89 Table J.2 – Harmonics content up to 25th in DSS 6 pulse connection(ideal rectangular current waveshape)
90 Table J.3 – Calculation factor comparison example
91 Table J.4 – Calculation factor comparison general factors
94 Bibliography
BS EN 61378-1:2011
$215.11