BS EN IEC 62271-112:2021
$167.15
High-voltage switchgear and controlgear – Alternating current high-speed earthing switches for secondary arc extinction on transmission lines
Published By | Publication Date | Number of Pages |
BSI | 2021 | 34 |
This part of IEC 62271 applies to AC high-speed earthing switches (hereafter termed HSES) designed for indoor and outdoor installation and for operation at service frequencies of 50 Hz and 60 Hz on systems having voltages of 550 kV and above. HSESs described in this document are intended to extinguish the secondary arc remaining after clearing faults on transmission lines by the circuit-breakers. For more detailed information on HSESs, refer to Annex A.
PDF Catalog
PDF Pages | PDF Title |
---|---|
2 | undefined |
5 | Annex ZA (normative)Normative references to international publicationswith their corresponding European publications |
7 | English CONTENTS |
8 | FOREWORD |
10 | 1 Scope 2 Normative references 3 Terms and definitions |
12 | Figure 1 ā Explanation of a multi-phase auto-reclosing scheme |
13 | 4 Normal and special service conditions 5 Ratings Figures |
15 | 6 Design and construction Figure 2 ā Timing chart of HSES and circuit-breakers |
16 | Tables Table 1 ā Nameplate information |
17 | 7 Type tests |
18 | Table 2 ā Standard values of rated induced currents and voltages |
20 | 8 Routine tests 9 Guide to the selection of HSESs (informative) 10 Information to be given with enquiries, tenders and orders (informative) 11 Transport, storage, installation, operating instructions and maintenance |
21 | 12 Safety |
22 | Annex A (informative) Background information on the use of HSESs |
23 | Figure A.1 ā Single-line diagram of a power system Figure A.2 ā Timing chart of the HSESs in relation to the transmission line circuit-breakers |
24 | Figure A.3 ā Typical timing chart showing the time between fault initiation and a successful re-close of the transmission line circuit-breakers |
25 | Table A.1 ā Comparison of earthing switches |
26 | Table A.2 ā Comparison of a four-legged reactor and HSES |
27 | Annex B (informative) Induced current and voltage conditions for other cases |
28 | Figure B.1 ā System condition to explain successive fault Figure B.2 ā Example of waveforms of delayed current zero phenomena |
29 | Table B.1 ā Preferred values for single-phase earth fault with delayed current zero phenomena in the presence of a successive fault |
30 | Figure B.3 ā Typical test circuit for electromagnetic coupling test-duty of a HSES with delayed current zero crossings Figure B.4 ā Typical test circuit for electrostatic coupling test-duty of HSES with delayed current zero crossings |
31 | Table B.2 ā Preferred values for multi-phase earth faults in a double-circuit system Table B.3 ā Preferred values for covering the cases of categories 0 and 1 |
32 | Bibliography |